Energy Conservation Tips - Industrial
(source - BEE)
THERMAL UTILITIES
Boilers
Preheat combustion air with
waste heat
(22 0C reduction in flue gas
temperature increases boiler
efficiency by 1%).
Use variable speed drives on
large boiler combustion air fans
with variable flows.
Burn wastes if permitted.
Insulate exposed heated oil
tanks.
Clean burners, nozzles,
strainers, etc.
Inspect oil heaters for proper
oil temperature.
Close burner air and/or stack
dampers when the burner is off
to minimize heat loss up the
stack.
Improve oxygen trim control
(e.g. -- limit excess air to
less than 10% on clean fuels).
(5% reduction in excess air
increases boiler efficiency by
1% or: 1% reduction of residual
oxygen in stack gas increases
boiler efficiency by 1%.)
Automate/optimize boiler blow
down. Recover boiler blow down
heat.
Use boiler blow down to help
warm the back-up boiler.
Optimize deaerator venting.
Inspect door gaskets.
Inspect for scale and sediment
on the water side
(A 1 mm thick scale (deposit) on
the water side could increase
fuel consumption by 5 to 8%).
Inspect for soot, flyash, and
slag on the fire side
(A 3 mm thick soot deposition on
the heat transfer surface can
cause an increase in fuel
consumption to the tune of
2.5%.)
Optimize boiler water treatment.
Add an economizer to preheat
boiler feed water using exhaust
heat.
Recycle steam condensate.
Study part-load characteristics
and cycling costs to determine
the most-efficient mode for
operating multiple boilers.
Consider multiple or modular
boiler units instead of one or
two large boilers.
Establish a boiler
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make a boiler
efficiency-maintenance program a
part of your continuous energy
management program.
Steam System
Fix steam leaks and condensate
leaks
(A 3 mm diameter hole on a pipe
line carrying 7 kg/cm2 steam
would waste 33 kilo liters of
fuel oil per year).
Accumulate work orders for
repair of steam leaks that can't
be fixed during the heating
season due to system shutdown
requirements. Tag each such leak
with a durable tag with a good
description.
Use back pressure steam turbines
to produce lower steam
pressures.
Use more-efficient steam
desuperheating methods.
Ensure process temperatures are
correctly controlled.
Maintain lowest acceptable
process steam pressures.
Reduce hot water wastage to
drain.
Remove or blank off all
redundant steam piping.
Ensure condensate is returned or
re-used in the process
(6 0C raise in feed water
temperature by economiser /
condensate recovery corresponds
to a 1% saving in fuel
consumption, in boiler).
Preheat boiler feed-water.
Recover boiler blowdown.
Check operation of steam traps.
Remove air from indirect steam
using equipment
(0.25 mm thick air film offers
the same resistance to heat
transfer as a 330 mm thick
copper wall.)
Inspect steam traps regularly
and repair malfunctioning traps
promptly.
Consider recovery of vent steam
(e.g. -- on large flash tanks).
Use waste steam for water
heating.
Use an absorption chiller to
condense exhaust steam before
returning the condensate to the
boiler.
Use electric pumps instead of
steam ejectors when cost
benefits permit
Establish a steam
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make a steam
efficiency-maintenance program a
part of your continuous energy
management program.
Furnaces
Check against infiltration of
air: Use doors or air curtains.
Monitor O2 /CO2/CO and control
excess air to the optimum level.
Improve burner design,
combustion control and
instrumentation.
Ensure that the furnace
combustion chamber is under
slight positive pressure.
Use
ceramic fibers in the case of
batch operations.
Match the load to the furnace
capacity.
Retrofit with heat recovery
device.
Investigate cycle times and
reduce.
Provide temperature controllers.
Ensure that flame does not touch
the stock.
Insulation
Repair damaged insulation
(A bare steam pipe of 150 mm
diameter and 100 m length,
carrying saturated steam at 8
kg/cm2 would waste 25,000 liters
furnace oil in a year.)
Insulate any hot or cold metal
or insulation.
Replace wet insulation.
Use an infrared gun to check for
cold wall areas during cold
weather or hot wall areas during
hot weather.
Ensure that all insulated
surfaces are cladded with
aluminum
Insulate all flanges, valves and
couplings
Insulate open tanks
(70% heat losses can be reduced
by floating a layer of 45 mm
diameter polypropylene (plastic)
balls on the surface of 90 0C
hot liquid/condensate).
Use waste heat for fuel oil
heating, boiler feed water
heating, outside air heating,
etc.
Use chiller waste heat to
preheat hot water.
Use heat pumps.
Use absorption refrigeration.
Use thermal
ELECTRICAL UTILITIES
Electricity Distribution System
Optimise the tariff structure
with utility supplier
Schedule your operations to
maintain a high load factor
Shift loads to off-peak times if
possible.
Minimise maximum demand by
tripping loads through a demand
controller
Stagger start-up times for
equipment with large starting
currents to minimize load
peaking.
Use standby electric generation
equipment for on-peak high load
periods.
Correct power factor to at least
0.90 under rated load
conditions.
Relocate transformers close to
main loads.
Set transformer taps to optimum
settings.
Disconnect primary power to
transformers that do not serve
any active loads
Consider on-site electric
generation or cogeneration.
Export power to grid if you have
any surplus in your captive
generation
Check utility electric meter
with your own meter.
Shut off unnecessary computers,
printers, and copiers at night.
Motors
Properly size to the load for
optimum efficiency.
(High efficiency motors offer of
4 - 5% higher efficiency than
standard motors)
Use energy-efficient motors
where economical.
Use synchronous motors to
improve power factor.
Check alignment.
Provide proper ventilation
(For every 10 oC increase in
motor operating temperature over
recommended peak, the motor life
is estimated to be halved)
Check for under-voltage and
over-voltage conditions.
Balance the three-phase power
supply.
(An imbalanced voltage can
reduce 3 - 5% in motor input
power)
Demand efficiency restoration
after motor rewinding.
(If rewinding is not done
properly, the efficiency can be
reduced by 5 - 8%)
Drives
Use variable-speed drives for
large variable loads.
Use high-efficiency gear sets.
Use precision alignment.
Check belt tension regularly.
Eliminate variable-pitch
pulleys.
Use flat belts as alternatives
to v-belts.
Use synthetic lubricants for
large gearboxes.
Eliminate eddy current
couplings.
Shut them off when not needed.
Fans
Use smooth, well-rounded air
inlet cones for fan air intakes.
Avoid poor flow distribution at
the fan inlet.
Minimize fan inlet and outlet
obstructions.
Clean screens, filters, and fan
blades regularly.
Use aerofoil-shaped fan blades.
Minimize fan speed.
Use low-slip or flat belts.
Check belt tension regularly.
Eliminate variable pitch
pulleys.
Use variable speed drives for
large variable fan loads.
Use energy-efficient motors for
continuous or near-continuous
operation
Eliminate leaks in ductwork.
Minimize bends in ductwork
Turn fans off when not needed.
Blowers
Use smooth, well-rounded air
inlet ducts or cones for air
intakes.
Minimize blower inlet and outlet
obstructions.
Clean screens and filters
regularly.
Minimize blower speed.
Use low-slip or no-slip belts.
Check belt tension regularly.
Eliminate variable pitch
pulleys.
Use variable speed drives for
large variable blower loads.
Use energy-efficient motors for
continuous or near-continuous
operation.
Eliminate ductwork leaks.
Turn blowers off when they are
not needed.
Pumps
Operate pumping near best
efficiency point.
Modify pumping to minimize
throttling.
Adapt to wide load variation
with variable speed drives or
sequenced control of smaller
units.
Stop running both pumps -- add
an auto-start for an on-line
spare or add a booster pump in
the problem area.
Use booster pumps for small
loads requiring higher
pressures.
Increase fluid temperature
differentials to reduce pumping
rates.
Repair seals and packing to
minimize water waste.
Balance the system to minimize
flows and reduce pump power
requirements.
Use siphon effect to advantage:
don't waste pumping head with a
free-fall (gravity) return.
Compressors
Consider variable speed drive
for variable load on positive
displacement compressors.
Use a synthetic lubricant if the
compressor manufacturer permits
it.
Be sure lubricating oil
temperature is not too high (oil
degradation and lowered
viscosity) and not too low
(condensation contamination).
Change the oil filter regularly.
Periodically inspect compressor
intercoolers for proper
functioning.
Use waste heat from a very large
compressor to power an
absorption chiller or preheat
process or utility feeds.
Establish a compressor
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make a
compressor
efficiency-maintenance program a
part of your continuous energy
management program.
Compressed air
Install a control system to
coordinate multiple air
compressors.
Study part-load characteristics
and cycling costs to determine
the most-efficient mode for
operating multiple air
compressors.
Avoid over sizing -- match the
connected load.
Load up modulation-controlled
air compressors. (They use
almost as much power at partial
load as at full load.)
Turn off the back-up air
compressor until it is needed.
Reduce air compressor discharge
pressure to the lowest
acceptable setting.
(Reduction of 1 kg/cm2 air
pressure (8 kg/cm2 to 7 kg/cm2)
would result in 9% input power
savings. This will also reduce
compressed air leakage rates by
10%)
Use the highest reasonable dryer
dew point settings.
Turn off refrigerated and heated
air dryers when the air
compressors are off.
Use a control system to minimize
heatless desiccant dryer
purging.
Minimize purges, leaks,
excessive pressure drops, and
condensation accumulation.
(Compressed air leak from 1 mm
hole size at 7 kg/cm2 pressure
would mean power loss equivalent
to 0.5 kW)
Use drain controls instead of
continuous air bleeds through
the drains.
Consider engine-driven or
steam-driven air compression to
reduce electrical demand
charges.
Replace standard v-belts with
high-efficiency flat belts as
the old v-belts wear out.
Use a small air compressor when
major production load is off.
Take air compressor intake air
from the coolest (but not air
conditioned) location.
(Every 50C reduction in intake
air temperature would result in
1% reduction in compressor power
consumption)
Use an air-cooled aftercooler to
heat building makeup air in
winter.
Be sure that heat exchangers are
not fouled (e.g. -- with oil).
Be sure that air/oil separators
are not fouled.
Monitor pressure drops across
suction and discharge filters
and clean or replace filters
promptly upon alarm.
Use a properly sized compressed
air storage receiver. Minimize
disposal costs by using
lubricant that is fully
demulsible and an effective
oil-water separator.
Consider alternatives to
compressed air such as blowers
for cooling, hydraulic rather
than air cylinders, electric
rather than air actuators, and
electronic rather than pneumatic
controls.
Use nozzles or venturi-type
devices rather than blowing with
open compressed air lines.
Check for leaking drain valves
on compressed air
filter/regulator sets. Certain
rubber-type valves may leak
continuously after they age and
crack.
In dusty environments, control
packaging lines with
high-intensity photocell units
instead of standard units with
continuous air purging of lenses
and reflectors.
Establish a compressed air
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make a
compressed air
efficiency-maintenance program a
part of your continuous energy
management program.
Chillers
Increase the chilled water
temperature set point if
possible.
Use the lowest temperature
condenser water available that
the chiller can handle.
(Reducing condensing temperature
by 5.5 0C, results in a 20 - 25%
decrease in compressor power
consumption)
Increase the evaporator
temperature
(5.50C increase in evaporator
temperature reduces compressor
power consumption by 20 - 25%)
Clean heat exchangers when
fouled.
(1 mm scale build-up on
condenser tubes can increase
energy consumption by 40%)
Optimize condenser water flow
rate and refrigerated water flow
rate.
Replace old chillers or
compressors with new
higher-efficiency models.
Use water-cooled rather than
air-cooled chiller condensers.
Use energy-efficient motors for
continuous or near-continuous
operation.
Specify appropriate fouling
factors for condensers.
Do not overcharge oil.
Install a control system to
coordinate multiple chillers.
Study part-load characteristics
and cycling costs to determine
the most-efficient mode for
operating multiple chillers.
Run the chillers with the lowest
energy consumption. It saves
energy cost, fuels a base load.
Avoid oversizing -- match the
connected load.
Isolate off-line chillers and
cooling towers.
Establish a chiller
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make a chiller
efficiency-maintenance program a
part of your continuous energy
management program.
HVAC (Heating / Ventilation / Air
Conditioning)
Tune up the HVAC control system.
Consider installing a building
automation system (BAS) or
energy management system (EMS)
or restoring an out-of-service
one.
Balance the system to minimize
flows and reduce blower/fan/pump
power requirements.
Eliminate or reduce reheat
whenever possible.
Use appropriate HVAC thermostat
setback.
Use morning pre-cooling in
summer and pre-heating in winter
(i.e. -- before electrical peak
hours).
Use building thermal lag to
minimize HVAC equipment
operating time.
In winter during unoccupied
periods, allow temperatures to
fall as low as possible without
freezing water lines or damaging
stored materials.
In summer during unoccupied
periods, allow temperatures to
rise as high as possible without
damaging stored materials.
Improve control and utilization
of outside air.
Use air-to-air heat exchangers
to reduce energy requirements
for heating and cooling of
outside air.
Reduce HVAC system operating
hours (e.g. -- night, weekend).
Optimize ventilation.
Ventilate only when necessary.
To allow some areas to be shut
down when unoccupied, install
dedicated HVAC systems on
continuous loads (e.g. --
computer rooms).
Provide dedicated outside air
supply to kitchens, cleaning
rooms, combustion equipment,
etc. to avoid excessive
exhausting of conditioned air.
Use evaporative cooling in dry
climates.
Reduce humidification or
dehumidification during
unoccupied periods.
Use atomization rather than
steam for humidification where
possible.
Clean HVAC unit coils
periodically and comb mashed
fins.
Upgrade filter banks to reduce
pressure drop and thus lower fan
power requirements.
Check HVAC filters on a schedule
(at least monthly) and
clean/change if appropriate.
Check pneumatic controls air
compressors for proper
operation, cycling, and
maintenance.
Isolate air conditioned loading
dock areas and cool storage
areas using high-speed doors or
clear PVC strip curtains.
Install ceiling fans to minimize
thermal stratification in
high-bay areas.
Relocate air diffusers to
optimum heights in areas with
high ceilings.
Consider reducing ceiling
heights.
Eliminate obstructions in front
of radiators, baseboard heaters,
etc.
Check reflectors on infrared
heaters for cleanliness and
proper beam direction.
Use professionally-designed
industrial ventilation hoods for
dust and vapor control.
Use local infrared heat for
personnel rather than heating
the entire area.
Use spot cooling and heating
(e.g. -- use ceiling fans for
personnel rather than cooling
the entire area).
Purchase only high-efficiency
models for HVAC window units.
Put HVAC window units on timer
control.
Don't oversize cooling units.
(Oversized units will "short
cycle" which results in poor
humidity control.)
Install multi-fueling capability
and run with the cheapest fuel
available at the time.
Consider dedicated make-up air
for exhaust hoods. (Why exhaust
the air conditioning or heat if
you don't need to?)
Minimize HVAC fan speeds.
Consider desiccant drying of
outside air to reduce cooling
requirements in humid climates.
Consider ground source heat
pumps.
Seal leaky HVAC ductwork.
Seal all leaks around coils.
Repair loose or damaged flexible
connections (including those
under air handling units).
Eliminate simultaneous heating
and cooling during seasonal
transition periods.
Zone HVAC air and water systems
to minimize energy use.
Inspect, clean, lubricate, and
adjust damper blades and
linkages.
Establish an HVAC
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make an HVAC
efficiency-maintenance program a
part of your continuous energy
management program.
Refrigeration
Use water-cooled condensers
rather than air-cooled
condensers.
Challenge the need for
refrigeration, particularly for
old batch processes.
Avoid oversizing -- match the
connected load.
Consider gas-powered
refrigeration equipment to
minimize electrical demand
charges.
Use "free cooling" to allow
chiller shutdown in cold
weather.
Use refrigerated water loads in
series if possible.
Convert firewater or other tanks
to thermal storage.
Don't assume that the old way is
still the best -- particularly
for energy-intensive low
temperature systems.
Correct inappropriate brine or
glycol concentration that
adversely affects heat transfer
and/or pumping energy.
If it sweats, insulate it, but
if it is corroding, replace it
first.
Make adjustments to minimize hot
gas bypass operation.
Inspect moisture/liquid
indicators.
Consider change of refrigerant
type if it will improve
efficiency.
Check for correct refrigerant
charge level.
Inspect the purge for air and
water leaks.
Establish a refrigeration
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make a
refrigeration
efficiency-maintenance program a
part of your continuous energy
management program.
Cooling towers
Control cooling tower fans based
on leaving water temperatures.
Control to the optimum water
temperature as determined from
cooling tower and chiller
performance data.
Use two-speed or variable-speed
drives for cooling tower fan
control if the fans are few.
Stage the cooling tower fans
with on-off control if there are
many.
Turn off unnecessary cooling
tower fans when loads are
reduced.
Cover hot water basins (to
minimize algae growth that
contributes to fouling).
Balance flow to cooling tower
hot water basins.
Periodically clean plugged
cooling tower water distribution
nozzles.
Install new nozzles to obtain a
more-uniform water pattern.
Replace splash bars with
self-extinguishing PVC
cellular-film fill.
On old counterflow cooling
towers, replace old spray-type
nozzles with new square-spray
ABS practically-non-clogging
nozzles.
If possible, follow
manufacturer's recommended
clearances around cooling towers
and relocate or modify
structures, signs, fences,
dumpsters, etc. that interfere
with air intake or exhaust.
Optimize cooling tower fan blade
angle on a seasonal and/or load
basis.
Correct excessive and/or uneven
fan blade tip clearance and poor
fan balance.
Use a velocity pressure recovery
fan ring.
Divert clean air-conditioned
building exhaust to the cooling
tower during hot weather.
Re-line leaking cooling tower
cold water basins.
Check water overflow pipes for
proper operating level.
Optimize chemical use.
Consider side stream water
treatment.
Restrict flows through large
loads to design values.
Shut off loads that are not in
service.
Take blowdown water from the
return water header.
Optimize blowdown flow rate.
Automate blowdown to minimize
it.
Send blowdown to other uses
(Remember, the blowdown does not
have to be removed at the
cooling tower. It can be removed
anywhere in the piping system.)
Implement a cooling tower
winterization plan to minimize
ice build-up.
Install interlocks to prevent
fan operation when there is no
water flow.
Establish a cooling tower
efficiency-maintenance program.
Start with an energy audit and
follow-up, then make a cooling
tower efficiency-maintenance
program a part of your
continuous energy management
program.
Lighting
Reduce excessive illumination
levels to standard levels using
switching, delamping, etc. (Know
the electrical effects before
doing delamping.)
Aggressively control lighting
with clock timers, delay timers,
photocells, and/or occupancy
sensors.
Install efficient alternatives
to incandescent lighting,
mercury vapor lighting, etc.
Efficacy (lumens/watt) of
various technologies range from
best to worst approximately as
follows: low pressure sodium,
high pressure sodium, metal
halide, fluorescent, mercury
vapor, incandescent.
Select ballasts and lamps
carefully with high power factor
and long-term efficiency in
mind.
Upgrade obsolete fluorescent
systems to Compact fluorescents
and electronic ballasts
Consider daylighting, skylights,
etc.
Consider painting the walls a
lighter color and using less
lighting fixtures or lower
wattages.
Use task lighting and reduce
background illumination.
Re-evaluate exterior lighting
strategy, type, and control.
Control it aggressively.
Change exit signs from
incandescent to LED.
DG sets
Optimize loading
Use waste heat to generate
steam/hot water /power an
absorption chiller or preheat
process or utility feeds.
Use jacket and head cooling
water for process needs
Clean air filters regularly
Insulate exhaust pipes to reduce
DG set room temperatures
Use cheaper heavy fuel oil for
capacities more than 1MW
Buildings
Seal exterior
cracks/openings/gaps with caulk,
gasketing, weatherstripping,
etc.
Consider new thermal doors,
thermal windows, roofing
insulation, etc.
Install windbreaks near exterior
doors.
Replace single-pane glass with
insulating glass.
Consider covering some window
and skylight areas with
insulated wall panels inside the
building.
If visibility is not required
but light is required, consider
replacing exterior windows with
insulated glass block.
Consider tinted glass,
reflective glass, coatings,
awnings, overhangs, draperies,
blinds, and shades for sunlit
exterior windows.
Use landscaping to advantage.
Add vestibules or revolving
doors to primary exterior
personnel doors.
Consider automatic doors, air
curtains, strip doors, etc. at
high-traffic passages between
conditioned and non-conditioned
spaces. Use self-closing doors
if possible.
Use intermediate doors in
stairways and vertical passages
to minimize building stack
effect.
Use dock seals at shipping and
receiving doors.
Bring cleaning personnel in
during the working day or as
soon after as possible to
minimize lighting and HVAC
costs.
Water & Wastewater
Recycle water, particularly for
uses with less-critical quality
requirements.
Recycle water, especially if
sewer costs are based on water
consumption.
Balance closed systems to
minimize flows and reduce pump
power requirements.
Eliminate once-through cooling
with water.
Use the least expensive type of
water that will satisfy the
requirement.
Fix water leaks.
Test for underground water
leaks. (It's easy to do over a
holiday shutdown.)
Check water overflow pipes for
proper operating level.
Automate blowdown to minimize
it.
Provide proper tools for wash
down -- especially self-closing
nozzles.
Install efficient irrigation.
Reduce flows at water sampling
stations.
Eliminate continuous overflow at
water tanks.
Promptly repair leaking toilets
and faucets.
Use water restrictors on
faucets, showers, etc.
Use self-closing type faucets in
restrooms.
Use the lowest possible hot
water temperature.
Do not use a central heating
system hot water boiler to
provide service hot water during
the cooling season -- install a
smaller, more-efficient system
for the cooling season service
hot water.
Consider the installation of a
thermal solar system for warm
water.
If water must be heated
electrically, consider
accumulation in a large
insulated storage tank to
minimize heating at on-peak
electric rates.
Use multiple, distributed, small
water heaters to minimize
thermal losses in large piping
systems.
Use freeze protection valves
rather than manual bleeding of
lines.
Consider leased and mobile water
treatment systems, especially
for deionized water.
Seal sumps to prevent seepage
inward from necessitating extra
sump pump operation.
Install pretreatment to reduce
TOC and BOD surcharges.
Verify the water meter readings.
(You'd be amazed how long a
meter reading can be estimated
after the meter breaks or the
meter pit fills with water!)
Verify the sewer flows if the
sewer bills are based on them
Miscellaneous
Meter any unmetered utilities.
Know what is normal efficient
use. Track down causes of
deviations.
Shut down spare, idling, or
unneeded equipment.
Make sure that all of the
utilities to redundant areas are
turned off -- including
utilities like compressed air
and cooling water.
Install automatic control to
efficiently coordinate multiple
air compressors, chillers,
cooling tower cells, boilers,
etc.
Renegotiate utilities contracts
to reflect current loads and
variations.
Consider buying utilities from
neighbors, particularly to
handle peaks.
Leased space often has low-bid
inefficient equipment. Consider
upgrades if your lease will
continue for several more years.
Adjust fluid temperatures within
acceptable limits to minimize
undesirable heat transfer in
long pipelines.
Minimize use of flow bypasses
and minimize bypass flow rates.
Provide restriction orifices in
purges (nitrogen, steam, etc.).
Eliminate unnecessary flow
measurement orifices.
Consider alternatives to high
pressure drops across valves.
Turn off winter heat tracing
that is on in summer.